Reprinted–Debugging and common troubleshooting of Yangxiu electric doors

Source: Thermal Control Circle

Debugging method and troubleshooting of Yangxiu electric door

1. Yangxiu DZW series electric actuator

1.1 Main technical parameters

Power supply: AC380V, 50Hz, three-phase three-wire system

Valve position signal: output 4~20mA

Protection level: IP55

Ambient temperature: -20℃~60℃

Output Power: 0.030~15KW

1.2 Operation

operate in the \”remote\” or \”local\” state respectively. When the power is turned on each time, it is in \”remote\”. If you need to perform \”local\” operation, click \”local\” ” button to switch the “Remote” status to “Present” \”Local\” state. At this time, the green luminous tube indicating the \”remote\” state goes out, and the red luminous tube indicating the \”local\” state lights up. The \”on\”, \”off\” and \”stop\” buttons for remote operations do not work and can only be operated in Operate the \”on\”, \”off\” and \”stop\” buttons on the local operation panel.

1.3 Precautions for adjustment

Check whether the grounding is reliable before turning on the power. Newly installed electric devices must be powered on for the first time. Check the motor phase sequence and whether the control circuit is correct to prevent the motor from running out of control.

1.4 Torque control mechanism adjustment

1.4.1 First adjust the closing torque.

1.4.2 According to the torque characteristic curve provided by the product, start from the small torque characteristic curve and the small torque value, and gradually increase the torque value until the valve is tightly closed. .

1.4.3 Adjust the torque. Generally, the torque in the opening direction is larger than the torque in the closing direction.

1.4.4 The above adjustments are all in the blankIt should be adjusted when there is no medium pressure and other factors. When there is pressure and temperature, attention should be paid to whether it can be closed tightly. If it is not closed tightly, it should be increased appropriately. The torque value shall be based on whether it is closed tightly or opened.

1.5 Stroke control mechanism adjustment

1.5.1 Close the valve tightly manually.

1.5.2 To disengage the stroke control mechanism, use a screwdriver to push the push rod of the stroke control mechanism and rotate it 90° to disengage the driving pinion from the counter gear set.

1.5.3 Use a screwdriver to rotate the \”close\” adjustment shaft in the direction of the arrow until the cam presses the spring pressure plate and causes the micro switch to operate. Then the close stroke is initially adjusted.

1.5.4 Loosen the ejector pin to ensure that the driving gear meshes correctly with the gears on both sides. To ensure the correct meshing, after loosening the ejector pin, you must use a screwdriver to Turn the adjustment shaft left or right.

1.5.5 Opening direction adjustment: After adjusting the closing direction, open the valve to the required position by hand, then disengage the stroke control mechanism and turn \”open\” Turn the adjustment shaft toward the arrow and rotate it in the direction of the arrow until the cam presses the spring plate and activates the micro switch. Then mesh the travel mechanism with the driving gear to complete the adjustment of the open direction stroke. You can repeat the above steps for adjustment.

2. Common fault handling

2.1 Analysis and troubleshooting methods of common faults of power phase loss

Actuator power supply phase loss is divided into two types: static phase loss and dynamic phase loss. A quick way to distinguish between these two types of phase loss is: in local mode, turn the operating button (black button) in the on or off direction. If the display immediately displays a \”power phase loss\” alarm, it is a static phase loss; if If the \”power phase loss\” alarm appears on the display after 1-2 seconds, it is a dynamic phase loss; there are differences in the cause analysis and troubleshooting methods for the two types of phase loss.
2.1.1 Cause analysis and troubleshooting methods for common faults of static phase loss
(1) Cause analysis: One phase of the three-phase power supply of the actuator is missing.
Troubleshooting method: Use an electric pen or multimeter to measure whether the voltage on the power terminal of the actuator is normal. If not, check whether the user\’s power distribution system and lines are working normally. If there is a fault, the user needs to eliminate it to ensure that the power supply is normal.
(2) Cause analysis: The control circuit board signal connection is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

(3) Cause analysis: The circuit components related to the power board are damaged.
Troubleshooting method: Replace the power board with the same model.

2.1.2 Analysis and troubleshooting methods of common faults of dynamic phase loss
(1) Cause analysis: The control circuit board signal connection contact is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

(2) Cause analysis: The AC contactor of the actuator is damaged.
Troubleshooting method: Replace the AC contactor with the same model.

(3) Cause analysis: The motor of the actuator is damaged.
Troubleshooting method: Replace the motor with the same model.

(4) Cause analysis: The circuit components related to the power board are damaged.

Troubleshooting method: Replace the power board with the same model.

2.2 Cause analysis and troubleshooting methods for common motor stall failures
(1) Cause analysis: The manual/electric switching device is locked and the motor is idling.
Troubleshooting method: Use the setter to reset the actuator, turn the handwheel of the actuator, and then electrically operate the actuator to switch to electric mode and run continuously; if it fails to switch to electric mode, it needs to be repeated multiple times. If the fault still cannot be solved after following the previous steps, please contact the factory.

(2) Cause analysis: The AC contactor controlling the motor is damaged or the sow head on the main control board is loose.
Troubleshooting method: Replace the damaged AC contactor or re-insert the plug-in on the main control board.

2.3 Analysis and troubleshooting methods of common power failure causes
(1) Cause analysis: The user\’s power fuse is burned out.
Troubleshooting method: The user checks the corresponding power distribution system and eliminates the fault.
(2) Cause analysis: The anti-surge power fuse on the power board is damaged.
Troubleshooting method: Replace the anti-surge power supply fuse of the same model.
(3) Cause analysis: The power transformer of the actuator is damaged.
Troubleshooting method: Replace the power transformer with the same model if it is damaged.
(4) Cause analysis: The control circuit board signal connection is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

2.4 Analysis and troubleshooting methods of common faults of motor overheating
(1) Cause analysis: The motor runs continuously for a long time and the temperature exceeds 130℃, the temperature switch automatically disconnects the protection .
Troubleshooting method: The actuator suspends work and can resume work only after the temperature of the motor drops.

2.5 Cause analysis and troubleshooting methods for common valve closing over-torque faults
(1) Cause analysis: Actuator closing over-torque protection parameter settingThe setting is too small.
Troubleshooting method: Use the setter to reset the closing torque protection value (increase it), operate the actuator electrically in local mode, and make it run back and forth for 2 to 3 full strokes, without the valve closing over-torque alarm occurring. Yes; if an alarm occurs, continue to adjust the shutdown protection value until the actuator operates normally.
(2) Cause analysis: The actuator selection does not match the on-site operating conditions.
Troubleshooting method: Choose a matching model to replace.
(3) Cause analysis: There are external factors that hinder the normal operation of the actuator (such as the valve being stuck).
Troubleshooting method: The user eliminates factors that affect the normal operation of the actuator.

2.6 Analysis and troubleshooting methods of common faults of over-torque valve opening (example with closing torque valve)

2.7 Valve position Analysis and troubleshooting methods of common overflow faults
(1) Cause analysis: The actuator valve position setting value is lost.
Troubleshooting method: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

2.8 Analysis and troubleshooting methods of common failures of valve position underflow
(1) Cause analysis: The actuator valve position setting value is lost.
Troubleshooting method: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

2.9 Analysis and troubleshooting methods of common faults when the remote switch cannot be controlled
(1) Cause analysis: The mode button on the electrical cover of the actuator is not in the correct remote position.
Troubleshooting method: Align the \”remote\” character of the mode button with a pointed protrusion mark next to the knob.
(2) Cause analysis: The relevant circuit components of the knob plate are damaged.
Troubleshooting: Replace the knob plate.
(3) Cause analysis: The user\’s remote control signal line is not wired correctly or the wiring is unreliable.
Troubleshooting method: Check the wiring to ensure it is correct and reliable.

2.10 Cause analysis and troubleshooting methods for abnormal display on the display screen after the actuator is powered on
(1) Cause analysis: The actuator resets abnormally after power on.
Troubleshooting method: a Use the setter to reset the actuator. b Cut off the power supply of the actuator, take out the backup battery of the actuator, wait for about 15-20 minutes and then power it on again. If it is still not normal, repeat the above process several times; replace the backup battery after normal display. cReplace the main control board with the same model.

2.11 Oil leaks from the surface of the actuator oil plug
(1) Cause analysis: The oil plug screw is loose.
Troubleshooting method: Tighten the oil plug screw and wipe away the oil stains.

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

Like (0)
华夏门网的头像华夏门网
Previous 2024年12月19日
Next 2024年12月19日

相关推荐

  • 2.0T,实用大七座,电动门,大尺寸3联屏,家用必备!

    日前,上汽大通MAXUS G70臻享版正式上市,售价为18.38万。新车各方面整体表现都可圈可点,是一款能满足家用的MPV车型。 优缺点速览: 优点: 1、造型大气 2、空间布局实用 缺点: 1、品牌认可度不足 外观方面,上汽大通MAXUS G70整体设计依旧十分大气,前脸格栅造型独特,两侧灯组造型也十分具有未来感,上方凸起于引擎盖的灯组造型也十分独特,颇有…

    电动门 2024年1月3日
    30
  • 特斯拉Model Y撞柱火災:電動門失靈,四人罹難於火海

    近日,一起涉及特斯拉Model Y電動汽車的嚴重交通事故在加拿大多倫多市中心發生,造成四人不幸喪生。據外媒報道,該事故發生在上個月,一輛Model Y在行駛過程中突然失控,猛烈撞擊瞭路邊的電線桿。 事故發生後,車輛迅速燃起熊熊大火,火勢迅速蔓延至整個車身。盡管消防員迅速趕到現場,但車輛已被大火完全包圍,救援工作異常艱難。在火勢被控制後,救援人員在車內發現瞭四…

    电动门 2024年11月21日
    30
  • 电动门控制电路

    有钱的老板们都买了别墅,独门独院,电梯啊,电动门这些都是他们标配了,作为维修电工们,自然就少不了跟电动门打交道了。所以我们认识电动门就从它的控制电路开始。 电动门的控制电路,实际上就是我们常见的电动机正反转控制电路,只是加了两个限位行程开关,能够自动控制停止。 在电路中采用按钮常闭触点和交流接触器的常闭触点来实现双重互锁保护,互锁程度较高。从电路中不难分析,…

    电动门 2023年11月8日
    80
  • The electric door was closing, but the child suddenly rushed out… The policeman risked his life and used his body to hold up the space.

    First day of school, first time entering school It is inevitable that some \”little flowers\” will not adapt to collective life. Recently, a thrilling scene occurred in…

    电动门 2025年1月6日
    10
  • 电动门增加门中门和透视窗的改装教程

    如何在使用15年的电动门上改装增加门中门和透视窗? 6月17日,昆明海顿自动门对一樘提升门进行改装,增加了一樘门中门,也就是在原有的大门上增开小门,这也是之前很多网友关心的问题,想把家里的车库门进行改装增加门中门和透视窗。 电动门改装增加门中门和透视窗在理论上是不分门洞大小都可以改装的,但需要在非常专业的技术工人在现场进行改装,而且要注意以下几点: 首先,改…

    电动门 2024年6月19日
    1290

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:admin@example.com

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信