Analysis of common problems at fire acceptance site – fire door 1

Analysis of common problems at fire acceptance site - fire door 1

Acceptance items:Fire separation

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 1:

The fire door is not equipped with a door closer, and the double fire door is not equipped with a sequencer.

When the normally open fire door is a sub-door, there is no door closer on the sub-door.

Relevant specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.5.1 The setting of fire doors should comply with the following regulations:

3. Except for tube well access doors and residential doors, fire doors should have a self-closing function.

\”Code for Construction and Acceptance of Fireproof Roller Shutters, Fireproof Doors, and Fireproof Windows\” GB50877—2014:

5.3.2 Normally closed fire doors should be equipped with door closers, and double-leaf and multi-leaf fire doors should be equipped with sequencers.

Analysis of common problems at fire acceptance site - fire door 1

Onsite problem description 2:

The evacuation doors in some parts are not equipped with Class A fire doors, such as the doors of the smoke prevention and exhaust machine room opening into the building, the doors of the evacuation aisles in the fire protection zone, Doors in underground garages opening to residential evacuation stairwells, doors on firewalls, etc.

The civil air defense area is adjacent to the fire protection zone. Only civil air defense doors are seen, and no Class A fire doors are installed.

Relevant specification requirements:

\”General Specifications for Building Fire Protection\” GB55037—2022:

6.4.2 Doors in the following locations should be Class A fire doors:

1. Doors set on the fire wall and doors set on the fire zone for evacuation corridors;

2. Set up a fire partition wall with a fire resistance limit of not less than 3.00hdoor;

3. Elevator room, The door connecting the evacuation stairwell to the garage;

4. Indoor doors opening to the front room of the evacuation corridor and evacuation doors in the evacuation room;

5. Doors leading from the warehouse to evacuation walkways or evacuation stairwells in multi-story Category B warehouses and underground, semi-underground and multi- and high-rise Category C warehouses.

6.4.5 Civilian air defense projects in daily use The fire resistance of protective doors, protective airtight doors, and airtight doors that replace Class A fire doors should not be lower than the requirements of Class A fire doors, and should not be used for evacuation exits in commonly used public places.

\”Code for Fire Protection Design of Buildings\” GB50016—2014 (2018 edition):

6.2.7 The doors of ventilation, air conditioning machine rooms and power transformation and distribution rooms that open into the building should use Class A fire doors, and the fire control room and other equipment rooms open to the doors in the building. Doors should be Class B fire doors.

\”Technical Specifications for Fire Water Supply and Fire Hydrant Systems\” GB50974—2014:

5.5.12 The fire pump room shall comply with the following requirements:

3. The fire pump room attached to the building should be separated from other parts by partition walls with a fire resistance rating of not less than 2.00h and floors of 1.50h. Its evacuation door should lead directly to the safety exit and open Doors to evacuation corridors should be Class A fire doors

\”Code for Fire Protection Design of Garages, Repair Garages and Parking Lots\” GB50067-2014:

6.0.7 For underground garages and semi-underground garages connected to residential basements, evacuation stairs in the residential part can be used for personnel evacuation; when it is not possible to directly enter the evacuation stairwell in the residential part, an evacuation staircase should be installed between the garage and the residential part. The connecting aisles should be separated by fire-resistant partition walls, and the doors of the garage opening to the aisles should be Class A fire-resistant doors

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 3:

The underground storage room does not use Class B fire doors;

The public kitchen in a public building is not separated from other parts as required by regulations.

Related specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.2.3 The following parts of the building should be separated from other parts by fire partition walls with a fire resistance rating of not less than 2.00h. Doors and windows on the wall should be Class B fire doors and windows. If there are difficulties, fire shutters can be used, but Shall comply with the provisions of Article 6.5.3 of this specification:

4. Affiliated warehouses in civil buildings and auxiliary rooms behind theaters;

5. In addition to kitchens in residential buildings, public kitchens in dormitories and apartment buildings and kitchens in other buildings;

Analysis of common problems at fire acceptance site - fire door 1

The picture comes from the Internet. If there is any infringement, please contact us to delete it.

Message at the end of the article:

Good-looking skins are the same, but interesting souls Pick one out of a million.

@binmayedu (firefighting) is with you, let’s be interesting together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

Like (0)
华夏门网的头像华夏门网
Previous 2024年12月25日
Next 2024年12月25日

相关推荐

  • 兗礦能源集團股份有限公司2024年自動防火門招標

    天眼查招投標信息提示,兗礦能源集團股份有限公司(物資供應中心)新增2024年自動防火門招標公告。 本次招標的自動防火門具體內容包括:本次招標為兗礦集團股份有限公司快速防火密閉門(自動防火門)公開招標項目,數量34套。其中:濟三煤礦6套,南屯煤礦1套,興隆莊煤礦和濟二煤礦各2套,趙樓煤礦4套,鮑店煤礦6套,石拉烏素煤礦和營盤壕煤礦各2套,金雞灘煤礦6套,轉龍灣…

    防火门 2024年9月3日
    40
  • 防火門知識總結,一文看懂!

    防火門 “能夠共同提供開口部一定程度的防火保護的任何防火門扇、門樘、五金及其它配件的組合。” 防火門按材質分類可以分為:木質防火門、鋼質防火門、鋼木質防火門以及其他材質防火門,我們常用的防火門是木質防火門和鋼質防火門。 防火門的構成解讀 · 防火門扇和門框 常用的木質防火門和鋼質防火門的門扇和門框,分別是用難燃木材和鋼材制作,門扇內若填充材料,則填充對人體無…

    防火门 2024年8月26日
    90
  • 防火门、疏散门、安全出入口能否设置门禁?

    四川消防工程公司-索安机电每周分享 防火门、疏散门、安全出入口能否设置门禁? 版权图片 答复:室内装修项目常常在疏散门、防火门、安全出入口设置门禁,发生火灾时不利于人员疏散,室内装饰增加的门禁系统,根据《火灾自动报警系统设计规范》GB50116-2013第4.10.3条,防火门、疏散门、安全出入口设置的门禁应连接至消防联动控制系统。 GB50116-2013…

    防火门 2023年12月12日
    330
  • 科普 | 聚焦“3·15”,學會辨別真假防火門!

    防火門是指在一定時間內能滿足耐火穩定性、完整性和隔熱性要求的門。它是設在防火分區間、疏散樓梯間、垂直豎井等具有一定耐火性的防火分隔物。 防火門除具有普通門的作用外,更具有阻止火勢蔓延和煙氣擴散的作用,可在一定時間內阻止火勢的蔓延,確保人員疏散,為逃生人員博得更多逃生時機。 那麼如何辨別真假防火門 給生命帶來更多保障 以下幾點給你答案 一是看一看銘牌 防火門銘…

    防火门 2024年9月11日
    50
  • 防火门及配件检测标准汇总

    防火门及配件检测哪些项目?检测周期多久呢?检测报告如何办理?测试方法有哪些?做检测,找百检! 检测项目: 尺寸偏差、灵活性(门扇开启力)、钢材(材料厚度)、防火合页(铰链)(耐火性能))、防火插销(耐火性能)、防火锁(耐火性能)、防火顺序器(耐火性能)、材料性能、耐火性能(防火锁)、配件性能、尺寸*限偏差、形位公差、可靠性、门扇质量、外观质量、灵活性、配合公…

    防火门 2024年5月2日
    10

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信