Part One
Various electric door wiring summary
Part 2
1. Rotork
1. For regulating actuator (IQM type):
4~41 short, 5~39 short Connect
26+, 27-Analog signal instructions
22 +, 23-valve position feedback signal
2. As a switch type electric valve (IQ type)
4~36 short circuit
5~34 short circuit (no short circuit when there is a stop command)
Command: On: 35, 5 Off: 33, 5
Feedback: On: Level 8, 9: 6, 7
Analog current feedback: 22+, 23—
Power failure feedback: 42, 43 (normally closed)
The instructions for imported electric doors are the same, and the feedback is: 15 16
2. Autork
1. Adjustable actuator (IKM type):
4~36 short circuit 5~39 short circuit
Analog signal instructions: 26+, 27—:
Valve position feedback signal: 22+, 23—
2. For switch type electric valve (IK type)
4~36 short circuit
5~34 short circuit (if there is a stop command, stop in the middle and do not short circuit)
Commands: On: 35, 5 Off: 33, 5
Stop: 34, 5
Feedback: On: 8, 9 Off: 6, 7
SimulationAmount of current feedback: 22+, 23—
Power failure feedback: 42, 43 (normally closed)
3. Auma
1. Use as a regulating electric valve
Commands: 2+, 3— Feedback: 24+, 23—
2. Use as a switch type electric valve
Command: On: 3, 11 Off: 2, 11, Stop: 11 4
Feedback: On: 39, 40 Off: 35, 36
4. Yangzhou Siemens Integration Electric door
1. LK series
(1), as a regulating electric valve
Analog instructions: 15+, 16-
Analog feedback: 13+, 14-
(2), as a switch type electric valve
Commands: On: 18, 21 Off: 19, 21
Feedback: On: 3, 4 Off: 1, 2
Analog feedback: 13+, 14—;
(3), power supply
AC380V:22(A), 23(B), 24(C);
AC220V:23(L), 24(N)
2. WK series (domestic technology)
For on-off electric valves
Commands: On: 3, 4; Off: 2, 4
Stop command 1, 4
Feedback: On: 17, 18; Off: 5, 6 p>
Analog feedback: 8+, 7— Power failure: 9 21
Self-maintaining: If X11 needs to be moved, unplug this plug
5. sipos execution agency
1. ECOTRON economical version: round plug connection with relay board (electric door)
Short circuit: 5, 6 terminals
Commands: On: 3, 1; Off: 2, 1
Emergency off: 9, 10 Stop: 4, 1
Feedback: On: 28, 29; Off: 32, 33 p>
Analog feedback: 7+, 8—
2. PROFITRON Professional:
Round plug-in connection with relay board (adjusting door)
Analog current command: 11+, 12-
Analog feedback: 7+, 8—
3. ECOTRON Economical
Direct connection with relay board (electric door);
Divided into four terminal strips: X3: 1, X3: 2, X1, and X2
Short circuit: terminals 18 and 19 (X3: 2 terminal strip)
Command: Open: 5, 3; (X3: 1 terminal strip)
Off: 4, 3 Stop: 6, 3
Feedback: Open feedback is connected to 1 and 2; (X2 terminal strip)
Close feedback to 5 and 6
Power supply is connected to X1 terminal block L1, L2, L3
4. PROFITRON Professional
Direct connection with relay board (regulating door);
Divided into four terminal strips: X3: 1, X3: 2, X1, and X2
Short circuit: 18, 15 terminals (X3: 2 terminal strip)
Analog instructions: 14+, 15- (X3: 2 terminal strip)
Analog feedback: 1+, 2- (X3:1 terminal strip)
Feedback on: 1, 2 (X2 terminal strip)
Close feedback: 5, 6
Power failure: 17, 18 (normally closed)
6. SCHIEBEL (jog control wiring)
Short circuit: 2~3 terminals (provide power)
Commands: On: 1, 4 Off: 1, 3
Current feedback: 23 (+) 24 (—)
7. ABB tune gate
Command: 34 (+) 33 (—)
Feedback: 35 (—) 36 (+)
Short circuit: 21~15 22~16 (used to provide remote control power supply) 21+ 22—(24V power supply provided internally)
ABB electric door
Commands: On 11 12 Off 13 14
Feedback: On 7 8 Off 9 10
ABB pneumatic door
Command: 11 12 (used to supply power to the control part)
Feedback: 31 32 (requires DCS to provide 24 power supply)
8. ROTORK made in Malaysia (non-integrated)
Power: 1 2 3
Close travel switch (normally open): 8 9
Open travel switch (normally open): 17 18
Current level inverse: 32— 23+
9. QP10POO—02 (ROTORK)
Command: Off 33 34 On 34 35
Feedback: On 15 16 Off 6 7
10. 1614X90—04 (ROTORK) Tune the door
Command: 22+ 13—
Feedback: 32+ 23—
Eleven. 1410—50 ROTOCK (domestically produced in Shanghai)
Gate adjustment commands: 22+ 13—
Feedback: 32+ 23—
Electric door inching
Command: On 39 37 Off 39 38
Feedback: On 15 16 Off 8 9
If self-holding is required, short circuit: 36~39
Power failure: 41 42
Twelve. Hunan Lisheng Information Equipment Co., Ltd.
Shorting: 1~2 1~5
Power: L1 L2 L3
Command: On 2 3 Level: 2 4
Feedback: On 6 8 Off: 7 8
Torque switch: on 11 9 off 11 10
Thirteen. ABB electric pump spoon tube door adjustment
Command: 26+ 27—
Feedback: 30+ 31—
Power supply: 14+ 15—
14. Electric doors produced by Jiangsu Baiyun Electric Machinery Factory
Power: 11 12 13 (Row A)
Commands: 3+ 4—
Feedback: 5+ 6— Far and near control switching: 7 8
(7 8 short-circuit remote control)
(Row B) Feedback: On 1 2 Off 3 4
Fifteen. PS wiring
Feedback: 7+ 8—
Command: 3+ 4—
16. Chongqing Sichuan Yi Electric Door
Power supply; L1 L2 L3 PE ground
24V internal power supply 21+ 22—
Command: Off 21 13 On 21 11
Feedback: Off 9 10 On 7 8
Short circuit: 22 ~ 12 24 ~ 14 (can not short circuit)
Chongqing Sichuan Yi Door Adjustment
Short circuit: 21~15 22~16
Command: 34+ 33—
Bit inversion: 36+ 35—
Seventeen. Changzhou Lanling integrated valve wiring
Command: open 6 8 Off 6 7 Stop 6 9
Feedback: On 5 6 Level 9 10
Short circuit 2 5 for near and far control
1+ 2—used to provide 24V power supply to the control board
18. Electric pump spoon tube wiring
Power supply (110V): 1 2
Emergency command: on 6 7 off 6 8
Current command: 9+ 10—
Feedback: 11+ 12—
Nineteen. Ricky RA series electric door
Command: Off 5 33 On 5 35
Feedback: Off 6 7 On 10 11
Short circuit: 5~34 (for self-maintaining) 4~36
RQ series door adjustment
Feedback: 22+ 23—
Command: 26+ 27—
Twenty.AUMA electric door wiring (non-integrated)
Close travel switch: 9 10 (normally closed) 11 12 (normally open)
Closing torque switch: 1 2 (normally closed)
Open travel switch: 13 14 (normally closed) 15 16 (normally open)
Opening torque switch: 5 6 (normally closed)
21. Tianjin Baili SMC series wiring diagram
Command: On: 34 17 Off: 34 18 Short: 20 35
(Instructions require DC24V power supply, 22+ 23—)
Feedback: On: 24 28 Off: 26 28 Fault: 16 15
(The terminal number is based on the number on the number tube)
22. Shanghai Automation Instrument No.11 Factory 1410-50-CA (wiring diagram)
Command: On 36 37 Off 36 38 Self-maintaining: 36 39
Feedback: On 10 11 Off 8 9 Failure: 41 42
23, JORDAN American Jordan wiring
Power supply: 1 live wire 2 neutral wire Command: 3 (+) 4 (—)
Feedback: 5 (+) 6 (—)
24. Yangzhou Electric Power Equipment Repair Factory Model: 040-0.5WZ Wiring
Current feedback: 4 (+) 5 (—) Command: Off 7 9
On: 8 9 9 (Hold) DC24V: 13+ 14—
25 , German EMG wiring
Electric door: Command: On: 20 3 Off: 20 4 Stop; 20 2 Short: 21 1
Feedback: Off: 5 7 On; 5 9
Failure: 5 10
Tiaomen: Command: 22+ 24— Feedback; 23+ 24—
26. Yangzhou Electric Power Equipment Factory Model: LU—10—1 strong>
Terminals: 1 2 3 (resistor)
11 5 Open stroke torque normally closed contact
11 6 Close stroke torque normally closed contact
11 8 Open stroke torque normally open contact
11 9 Close stroke torque normally open contact
7 torque normally open common point
D1 D2 D3 Motor power supply 380V
Note: For reference only, the actual instructions shall prevail.
Part 3
1 RAGA electric door terminal block:
Open command: 5 –35
Close command: 5–33
Open feedback: 6–7
Close feedback: 10–11
Fault: 42 –43 p>
4-36, 5-34 short circuit
2 ABB electric door terminal block:
Open command: 21 –11
Close command: 23–13
Feedback on: 7–8
Feedback off: 9 –10
Fault: 4 –5
22—12, 24—14 short circuit
3 British ROTORK electric door terminal block:
Open command: 5 –35
Close command: 5–33
Open feedback: 15–16
Close feedback: 6 –7
Fault: 24 –41
4–36 , 5-34 short circuit
4 EMG two-position electric door terminal block:
Open command: 4 –20
Off Command: 3–20
Enable feedback: 5–9
Related feedback: 5 –7
Fault: 5 –10
1–21 short circuit
5 EMG adjustable electric door terminal block:
Command: 22 –24
Feedback: 23….24
Close feedback: 5…7
Open feedback: 5…9
Fault: 5 –10
1–21 2…20 short circuit
6 Jordan adjustable electric door terminal blocks:
Commands: 3…4
Feedback: 5…6
Power: 1…2
7 AUTORK (IKM) Electric door terminal block:
Commands: 26 –27
Feedback: 22—23
Open feedback: 6—7
Close feedback: 8—9
5-39, 4-41 short circuit
8 AUTORK (IK) electric door terminal block:
Open command: 5–35 p>
Guanzhifeed: 5—33
Feedback on: 8—9
Feedback off: 6–7
Fault: 42 –43
4-43 short circuit
9 AUTORK (IQ) electric door terminal block:
Open command: 5–35
Close command: 5—33
Open feedback: 8—9
Close feedback: 6–7
Fault: 42 –43 p>
4—36 5—34 short circuit
10 AUTORK adjustable type
Instructions: 26 –27
Feedback: 22—23
Feedback: 6—7
Open feedback: 8—9
Fault: 4 –5
5-39, 4-41 short circuit
11 RAGA adjustable type
Command: 26 –27
Feedback: 22—23
Feedback: 6—7
Open feedback: 10–11
Fault: 4 2 –43
5—39, 4—41 short Continue
12 Shangyi Tiaomen Adjustable Type
Command: 26 –27
Feedback: 22—23
Feedback: 6—7
Open feedback: 8—9
Fault: 4 2 –43
5-39, 4-41 short circuit
13 AUMA two-position electric door terminal block:
Open command: 3 –11 p>
Close command: 2–11
Feedback on: 39–40
Feedback off: 35 –36
Fault: 14 –15
Yangxiu valve two-position electric slow door opening:
Reference: On, 3, 4
Off, 2, 4
Feedback: On, 17, 18
Off, 5, 6
Failure, 9, 21
Far away, 10, 11: self-maintained, 19, 20:
Power supply: 220VAC, 24L, 12N
Ecott:
Refer to today: open, 3, 1
Off, 4, 1
Feedback: On , 8, 9
Off, 6, 7
Failure, 12, 13
14.15 Valve position
Far away, 10, 11: Self-maintained, 19, 20:
Part 4
1.ROTORK
1 , as an adjustable actuator (IQM type)
4-41 short circuit 5,39 short circuit
26, 27, Analog signal instructions
22, 23, valve position feedback signal
2. For switch type electric valve (IQ type)
4,36 short circuit 5,34 short circuit (if there is a stop command, do not short circuit during the stop)
Command: On: 35, 5 Off: 33, 5
Feedback: On: 8, 9 Off: 6, 7
Analog current feedback: 22, 23 ,
Power failure feedback: 42, 43 (normally closed)
二Autork
1 for regulating actuator (IKM type): p>
,36 short circuit 5, 39 short circuit 4
Analog signal instructions: 26, 27,
Valve position feedback signal: 22, 23,
2 switch type electric valve (IK type)
4,36 short circuit 5,34 short circuit (stop in the middle if there is a stop command) No short circuit)
Command: On: 35, 5 Off: 33, 5 Stop: 34, 5
Feedback: On: 8, 9 Off: 6, 7
Analog current feedback: 22, 23,
Power failure feedback: 42, 43 (normally closed)
3. Auma
1 for regulating electric valve
Instruction: 2,, 3, feedback: 24,, 23, 2 for on-off electric valve
Commands: On: 3, 11 Off: 2, 11 Stop: 11, 4
Feedback: On: 39, 40 Off: 35, 36
4. Yangzhou Siemens integrated electric door
1. LK series
1), as a regulating electric valve
Analog instructions: 15,, 16,
Analog feedback: 13,, 14,
2) As a switch type electric valve:
Command: On: 18, 21 Off: 19, 21
Feedback: On: 3, 4 Off: 1, 2
Analog feedback: 13, 14 ,
3) Power supply
AC380V:22(A), 23(B), 24(C)
1/4 page
AC220V:23(L), 24(L)
2.MK series (domestic technology)
For switch type electric valve;
19,20 short circuit
Commands: On: 3, 4 Off: 2, 4 Stop: 1, 4
Feedback: On: 17, 18 Off: 5, 6
Analog feedback: 8, 7, power failure: 9, 21
Self-maintaining: If X11 needs to be moved, unplug this plug
5. Sipos actuator
1. ECOTRON economical type: round plug-type connection with relay board(Electric door) Short circuit: 5, 6 terminals
Command: Open: 3, 1 Close: 2, 1 Emergency close: 9, 10 Stop: 4, 1 Feedback: Open: 28, 29 Off: 32, 33 Analog feedback: 7, 8,
2. PROFITRON professional type: circular plug-type connection with relay board (adjusting door)
Analog current command: 11, 12,,, 8, Analog feedback: 7
3. ECOTRON economical type: direct connection with relay board (electric door)
Divided into four terminal strips: X3:1, X3:2, X1, and X2
p>
Terminals 18 and 19 (X3: 2 terminal strip) short circuit:
Command: On: 5, 3 Off :4, 3 Stop: 6, 3 (X3:1 terminal strip)
Feedback: On: 1, 2 Off: 5, 6 (X2 terminal strip)
The power supply is connected to X1 terminal block L1, L2, L3
4. PROFITRON Professional: direct connection with relay board (adjusting door)
p>
Divided into four terminal blocks: X3:1, X3:2, X1, and X2
Short-circuit: 18, 15 terminals ( X3: 2 terminal strip)
Analog instructions: 14, 15, (X3: 2 terminal strip)
Analog feedback: 1,, 2, (X3: 1 terminal strip)
p>
Open feedback: 1, 2 (X2 endsub-row)
Close feedback: 5, 6
Power failure: 17, 18 (normally closed)
Six (SCHIEBEL (jog control wiring)
Short circuit: terminals 2 and 3 (provide power)
Command: On: 1, 4 Off: 1, 3
Current feedback: 23,, 24,
Seven (ABB Adjustment Gate
Command: 34,, 33,
Feedback: 35,, 36,
Short-circuit: 21,15, 22,16 (used to provide Remote control power supply)
21,, 22, (24v power supply provided internally)
ABB electric door
Command: open 11, 12, close 13, 14
Page 2/4
Feedback: On 7, 8, Off 9, 10
ABB pneumatic door
Instructions: 11, 12 (used to supply power to the control part)
Feedback: 31, 32 (requires DCS to provide 24v power supply)
Eight (Malaysian ROTORK (not one-piece) )
Power: 1, 2, 3
Close travel switch (normally open): 8, 9
Open travel switch (normally open): 17, 18
Current bit inversion: 32, 23,
Nine(QP10POO,02(ROTORK)
Command: Off 33, 34, On 34, 35
Feedback: On 15, 16, Off 6, 7
Ten (1614X90-04(ROTORK) door adjustment
,, 13, command: 22
Feedback: 32,, 23,
November, 1410,50 RORORK (Made in Shanghai)
Gate adjustment instructions: 22+, 13,
Feedback: 32,, 23,
Electric door jog
Command: open 39, 37, close 39, 38
Feedback: On 15, 16, Off 8, 9
If self-holding is required, short-circuit: 36,39
Power failure: 41, 42
Twelve, Hunan Lisheng Information Equipment Co., Ltd.
Short: 1,2, 1,5
Power supply: L1 L2 L3
Command: On 2, 3 Off 2, 4
Feedback: On 6, 8, Off 7, 8
Torque switch: on 11, 9, off 11, 10
Thirteen, ABB electric pump spoon tube door adjustment
Instructions: 26,, 27,
Feedback: 30,, 31,
Power: 14,, 15,
Fourteen, electric door produced by Jiangsu Baiyun Electric Machinery Factory
Power supply: 11, 12, 13 (row A)
Command: 3,, 4,
Feedback: 5,, 6, far and near control switching: 7, 8 (7, 8 short for remote control)
Page 3/4
B row feedback: On 1, 2, Off 3, 4
p>
Fifteen, PS wiring
Feedback: 7,, 8,
Instructions: 3,, 4,
Sixteen, Chongqing Sichuan Electric Electric Door
Power supply: L1 L2 L3 PE ground
24V internal power supply: 21,, 22,
Command: Off 21, 13, On 21, 11
Feedback: Off 9, 10, On 7, 8 p>
Short-circuit: 22, 12, 24, 14 (can it not be short-circuited)
Chongqing Sichuan Yi Adjusting Door
Short connections: 21,15, 22 ,16
Command: 34,, 33,
Bit inversion: 36,, 35,
Seventeen, Changzhou Lanling integrated valve wiring
Command: open 6, 8, close 6, 7, stop 6, 9
Feedback: Open 5, 6 Off 9, 10
2,5 is used for near and far control short circuit:
1, 2, used to provide 24V power supply for the control board
Eighteen, electric pump spoon tube wiring
Power supply (110V): 1, 2
Emergency command: open 6, 7, close 6, 8
Current command: 9,, 10,
p>
Feedback: 11, , 12,
Nineteen, Ruiji RA series electric door
Command: off 5, 33, on 5, 35
Feedback: Off 6, 7, On 10, 11
Short: 5,34 (for self-holding) 4,36
RO series
Feedback: 22,, 23,
Instructions: 26,, 27,
Twenty, AUMA electric door wiring (non-integrated) p>
Close travel switch: 9, 10 (normally closed) 11, 12 (normally open)
Close torque switch: 1, 2
Open travel switch: 13, 14( Normally closed) 15, 16 (normally open)
Open torque switch: 5, 6 (normally closed)
(for production examination only, subject to the book of the executing agency)
Disclaimer: The content published on this platform is marked as original. . Reposted and shared contentThe content is for learning purposes only and is for reference only and does not represent my own views and positions. If there is any infringement, please contact us to delete it. Welcome all colleagues to communicate and learn together!