Fire door deformation, alarm host failure… Reporters followed the fire department to continuously expose a number of fire hazards

In accordance with the work requirements of the fire safety \”big investigation, big exposure, big rectification\” action, the reporter followed the Chengdu fire expert team and continued to visit some crowded places in the High-tech Zone, Dujiangyan City, Pidu District, and Xinjin District Undercover inspections were conducted, and a total of 8 public entertainment venues were inspected, and 32 fire hazards were found. The hidden hazards are now being exposed, and expert interpretations of some of the hazards are provided.

High-tech Zone

Catering venues: CapitaLand Tianfu, 6th Floor, No. 388 Tianren Road, Wuhou District, Chengdu

( 1) Many fire doors in this place were deformed and the fire door sequencer failed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Basis: This item violates the provisions of Article 16 of the Fire Protection Law of the People\’s Republic of China: Agencies, groups, enterprises, institutions and other units shall implement the following fire safety regulations Responsibilities: Configure fire-fighting facilities and equipment in accordance with national and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure they are intact and effective.

Expert interpretation: This place is a large commercial complex. There are many fire doors deformed and fire door sequencers malfunctioning in the place, including the kitchen and the fire doors leading to the stairwell.

(2) Many of the evacuation indicator lamps that maintain visual continuity in this place are faulty and partially blocked, and there are no signs under the fire shutters.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) Tables and chairs are set up in front of an evacuation door in this place, and items stacked in the stairwells and evacuation passages affect safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) Many air ducts and water pipes passing through fireproof partition walls in this place have not been fireproofed and sealed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(5) A lighting fixture on the stairwell floor of the site was faulty, and a safety exit sign lighting fixture was blocked by an air duct.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Shopping mall: Suning Plaza City Outlets ( Tianfu Overpass Store), the first floor of No. 8, North Section of Tianfu Avenue, High-tech Zone, Chengdu

(1) There are many safety exit evacuation doors, stairwells, and evacuation corridors where items are piled up in front of the site. The impact of installing latches on the evacuation doors Evacuate safely

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The evacuation doors of many shops in this place cannot lead directly to the outdoor ground or evacuation stairwells, nor to evacuation aisles, and items are piled under the fire-proof roller shutters. , no flag set.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: Some businesses in this place Stores are equipped with fire-proof roller shutters and other parts to divide fire protection zones. Multiple store evacuation doors cannot lead directly to the outdoor ground or evacuation stairwells, nor do they lead to evacuation aisles. One or more stores must be passed to reach the safety exit. Stores exist Nested evacuation. The evacuation of people from indoor rooms should ensure that the risk is reduced step by step. When indoor rooms are set up in nested (sleeved) configurations, the internal rooms In the event of a fire, you must pass through another dangerous area to reach the evacuation aisle or safety exit, and there is a certain risk. The key is that if the external room catches fire, it will directly block the safe evacuation of the internal room.

(3) The door closers and sequencers of many fire doors in this place were faulty or missing, and one fire door in this place was replaced with an ordinary door.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The selection of many evacuation indicator lamps in this place is incorrect, and the installation direction of the evacuation indicator lamps is inconsistent with the actual evacuation plan.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Dujiangyan City

1. Passenger Transport Center: Dujiangyan Passenger Transport Center, 1st Floor, No. 76, Yingbin Road, Dujiangyan City, Chengdu

(1) The number of fire extinguishers in the outbound passage of this site is insufficient, and the spacing between them is greater than the specification requirements.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The evacuation indicator lamp of the outbound passage of the site failed, and the power cord of the evacuation indicator lamp was not protected by a metal tube.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) There are no safety exit sign lamps installed above the evacuation door in the entrance hall and exit entrance of this place, and there are hanging lights above the evacuation door at the entrance entrance. Installing locks affects safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) E-bikes are parked in the outbound passage of this place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert Interpretation: This place is a multi-story public building, which is a densely populated place. Parking electric bicycles on the evacuation passage out of the station violates Article 7.8.2 of the \”Fire Safety Management of Densely Populated Places\” GB/T40248-2021 Article: Electrical fire safety management should meet the following requirements: Parking and charging of electric bicycles is strictly prohibited in crowded places.

2. Hotels: Huahai Hot Spring Hotel (Dujiangyan Scenic Area Branch), Guankou, Dujiangyan City, Chengdu. 2nd Floor, No. 12, No. 151, Upper Zoumahe East Road, Taiping Community

(1) The evacuation door from the corridor leading to the outer corridor of the place did not open in the evacuation direction.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: The evacuation door is a door set in each room in the building that directly leads to the evacuation corridor or a door on the safety exit. In order to avoid the panic and crowding of the crowd in the event of a fire, the evacuation door The door leaf cannot be opened, and the evacuation door is required to be opened in the evacuation direction. The place is located on the second floor of a multi-story public building. , there are two safety exits leading to the outer corridor, and the evacuation door of one of the safety exits leading to the outer corridor does not open in the evacuation direction.

(2) The electrical wiring between the linen in this place is not arranged in a standardized manner. and installation, the smoke detector was not installed at the top, and there were holes in the fireproof partition wall between the room and the corridor that were not fireproofed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) The fire alarm host of the place had a backup power failure, and a smoke detector reported a fire alarm.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The evacuation door leading to the stairwell in this place does not open in the evacuation direction. There is no safety exit sign lamp above the evacuation door. The above-ground and underground parts of the stairwell are connected, and the emergency lighting lamps in the stairwell are missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Pidu District

Expressway Service Area: Ande Service Area (Rongchang Expressway (Chengdu direction), Chengdu Pidu District Chengguan Expressway Ande Service Area (Rongchang Expressway Chengdu direction)

(1) One of the evacuation indicator lamp hanging chains at the site was broken, and one of the smoke detectors The dust cover of the device was not removed in time and the sprinkler head was installed incorrectly.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) Fire extinguishers and disinfectants in this place Fire hydrants were not regularly inspected.

Interpretation: This place is open to the public and is an indoor place for commercial operations. It is a crowded place. The fire hydrants and fire extinguishers in this place are not regularly inspected. This is a violation. \”Fire Protection Law of the People\’s Republic of China\” Tenth Article 6: Agencies, groups, enterprises, institutions and other units shall perform the following fire safety responsibilities: configure fire protection facilities and equipment in accordance with national standards and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure that they are intact and effective. /p>Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) One of the safety exits in the place is locked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

2. Nursing home: Yijin Nursing Home, No. 71, Shunhe East Street, Pidu District, Chengdu

(1) A storage room is provided in the enclosed stairwell of this place. p>Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The kitchen of this place is not completely separated from other parts by fireproof partition walls and fireproof doors and windows, and the evacuation door in the kitchen is locked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) Many smoke detectors in the place reported fire alarms, the alarm host had a large number of faults, and the fire-fighting equipment was not regularly inspected. Maintenance.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: This place is a multi-story public building with automatic fire alarm systems, fire hydrant systems, automatic sprinkler systems, etc. There are a large number of host failures and the fire-fighting equipment has not been regularly inspected. Maintenance will cause fire-fighting facilities to be unable to operate in the event of a fire, causing the fire to expand and spread.

(4) Some fire door closers and sequencers in this place are faulty, and some floor display lamps are not installed in the stairwell. No safety exit sign lights are installed above the evacuation door.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Xinjin District

1. Hospital outpatient building: Xinjin District People\’s Hospital, No. 149 Wujin West Road, Xinjin District, Chengdu City Floor 1~2

(1) The evacuation door on the first floor of a stairwell in this place did not open in the evacuation direction, there were no safety exit sign lamps above many evacuation doors, and the door closers of some fire doors were missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) There is no automatic fire extinguishing facility in the lobby on the first floor of this place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(三) Objects were piled in the stairwell and the evacuation door on the first floor of the place. An evacuation door was padlocked on the outside, causing the evacuation door to not open normally. Resting chairs were set up at the evacuation door to block the evacuation exit, and individual evacuation indicator lights were blocked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) A storage room is provided in an evacuation stairwell on the first floor of the place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

2. Training institution: Xuri Dongsheng Education, No. 96 Wujin South Road, Xinjin District, Chengdu Bell Tower 3rd Floor

(1) There are no audible and visual alarms, manual alarm buttons and fire broadcasts in this place.

Expert interpretation: This place is equipped with an automatic fire alarm system and automatic fire alarm system. Sprinkler system, fire hydrant system, evacuation indication system, etc. The fire detector installed in the automatic fire alarm system is an automatic trigger alarm device, while the manual fire alarm button is a manual trigger alarm device. In the design, both automatic fire alarm systems should be equipped with fire alarm devices. Sound and light alarms are used to sound the alarm in the event of a fire. Its main purpose is to alert personnel in the event of a fire and warn personnel in a timely manner. Evacuation. When a fire occurs, everyone should be informed as soon as possible. At the same time, in order to avoid crowding at evacuation passages and exits due to mistimed evacuation, emergency broadcasts are required to be broadcast to the entire building at the same time after the fire is confirmed. The inspection found that the important components of the automatic fire alarm system were missing in the premises: audible and visual alarms, manual alarm buttons and fire broadcasts.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The fire door sequencer in this place is missing, and the setting of the latch affects safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) The fire hydrant button in this place is missing, and the two fire hydrant valves are faulty and cannot be opened normally.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The positive pressure air supply vent louvers in the front room of the stairwell of this place were damaged, the normally closed air valve was not reset in time, and the emergency lighting fixtures in the stairwell were missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Basis: This item violates the provisions of Article 16 of the Fire Protection Law of the People\’s Republic of China: Agencies, regiments Entities, enterprises, institutions and other units shall perform the following fire safety responsibilities: configure fire protection facilities and equipment in accordance with national standards and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure they are intact and effective.

Chengdu. Daily Jinguan News Reporter Xu Songming Picture Xu Songming Chengdu Fire Protection Editor Liu Yang Editor Dai Aicen Reviewer Zhu Guangze Cao Yuyang

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

Like (0)
华夏门网的头像华夏门网
Previous 2025年1月20日
Next 2025年1月20日

相关推荐

  • 云投诉 | 消防通道防火门常开、电线接头暴露在外 消费者报料成都光环多处安全隐患

    近日,封面新闻云投诉平台收到多个消费者关于成都光环购物公园(以下简称“成都光环”)的报料。家住成都市成华区的周先生表示,6月22日上午听说成都光环开业,第一时间就去逛了下,因为自己从事建筑设计行业,在商场逛的时候发现场内多个消防通道的防火门一直开着,自己逛着很没有安全感。家住仁恒滨河湾的王女士表示,听说家附近的成都光环开了,23号去逛了下,在商场里待了差不多…

    防火门 2024年7月18日
    80
  • Is the fire door that can\’t be burned?

    Fire door, , also known as\” the door of life \” \” span style = \”color: #000000; –tt-darkmode-color: #A3A3A3;\”> evacuation staircase, vert…

    防火门 2025年2月5日
    00
  • 防火窗指什么?哪种条件下需要设置防火窗呢?

    防火窗是指由钢窗框、钢窗扇和防火玻璃制成的能隔离和防止火灾蔓延的窗户。   设置要求:   1.当窗台墙不满足0.8m要求时,如果没有实心墙,需要用防火窗隔开。   2.当两栋建筑不满足消防距离,且在侧防火墙上开窗时,按建筑规范第5.2.1条规定,需设置甲级消防窗。   3.如果高层公寓只有一个疏散梯,应设置防火窗。第6.1.1条高规。   常见的防火窗有哪…

    防火门 2023年11月5日
    330
  • 木质防火门和钢质防火门的区别是什么?选择防火门要注意什么

    防火门主要有木质和钢质两种,那么木质防火门和钢质防火门的区别是什么呢?快来跟小啄一起看看吧~ 一、木质防火门和钢质防火门的区别是什么 1、材质不同 木质防火门:使用木材或木制品加工制作而成的,通常木材经过了防火阻燃处理。 钢质防火门:使用钢制材料加工制作而成的。 2、重量不同 木质防火门:比较轻便。钢质防火门:相对而言会更加笨重些。 3、外观不同 木质防火门…

    防火门 2023年10月10日
    90
  • 封窗选购攻略,看完老板被坑不了你

    1、什么是断桥铝 断桥铝是两面为铝材,中间有塑料型材腔体做断热材料,做成隔热型的铝材, \”桥\”就是指隔热条,主要用来隔绝室内室外的热量传递,达到保温隔热的作用√不管是预算还是性能方面,如果追求性价比断桥铝完全足够了。 断桥铝横截面 2、什么是系统窗 系统窗也是断桥铝门窗,只不过综合水密性、气密性、抗风压、隔热、隔音、手感等因素,进…

    防火门 2024年6月9日
    50

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:admin@example.com

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信